11 / 16
11 / 16
21
21

Hybrox

Outdoor air source heat pump

Whether for energy-efficient new builds or challenging refurbishments: the Hybrox air/water heat pump series offers the right solution for every project. Available in 3 models (11/16/21), with an output range of 10 - 18kW, it covers a broad spectrum - with R290 Natural Refrigerant for efficient heating and cooling and with a strong focus on simple installation and smart control.

2

2 Year
Warranty*

Flexible for new builds, renovations and commercial properties

Whether an apartment building or commercial property - the Hybrox series is suitable for every requirement.

Smart & Digital

App control via myUplink, simple PV integration possible, Smart Grid Ready and compatible with BACnet and Modbus TCP.

Compact & Lightweight

Quick to install, well thought-out transport concept - perfect for installers.

Sound-optimized

For quiet operation even in sensitive residential areas.

Sustainable

Future-proof and environmentally friendly with R290 Natural Refrigerant

  • Perfect for high temperature heating systems

  • Quiet & compact

  • Flow temperatures up to 78°C - even at -22°C

  • Cascadable up to 4 units

  • Perfect for high temperature heating systems

  • Quiet & compact

  • Flow temperatures up to 78°C

  • BACnet, Modbus TCP, PV-ready & Smart Grid Ready

  • Cascadable up to 4 units (72kW)

*Subject to Terms & Conditions
Luxtronik wall controller

The Luxtronik indoor weather-compensated controller enables precise control and can be individually combined with various units and accessories on the market. Each unit includes a high-efficiency circulation pump and flow sensor as standard.

Featuring a full graphic display with intuitive menu navigation, all operating modes are individually programmable with runtime-optimised and heat demand-dependent compressor control. An outdoor temperature sensor, operating hours counter and diagnostic programme with fault memory allow heating performance to be optimally adjusted and monitored.

Additional features include screed heating, pump optimisation, control of several heat generators, mixing circuit control, data logger, commissioning assistant, holiday mode and rapid domestic hot water heating, with network-compatible USB interface and multilingual support.

Downloads

What are the benefits of air source heat pumps?

Air source heat pumps are the versatile, energy-efficient solution for modern heating and cooling systems, delivering exceptional performance and low running costs for commercial properties, apartment blocks, and new build developments.

Exceptional energy
efficiency and cost savings

Air source heat pumps deliver outstanding energy efficiency, significantly reducing heating costs compared to traditional gas boilers or electric heating systems. The Modutherm range achieves COPs up to 5.55 and A+++ energy efficiency ratings, meaning they produce over five times more heat energy than the electricity they consume. The Hybrox series (10-18kW) achieves COP up to 5.55 at A7/W35 conditions, whilst the AW290 range (35-100kW) delivers COP up to 4.4. This exceptional efficiency translates directly to lower energy bills and reduced carbon emissions. Air source heat pumps extract renewable heat from outdoor air, even at temperatures as low as -22°C, making them reliable year-round heating solutions for UK climates. With natural R290 refrigerant that has a Global Warming Potential of just 3 and zero Ozone Depletion Potential, these systems offer both economic and environmental benefits that align with net-zero carbon targets and increasingly stringent building regulations.

Versatile heating and cooling capability

Air source heat pumps provide both heating and cooling from a single system, offering year-round climate control and exceptional value for money. The AW290 range delivers 35-100kW heating capacity and 8.6-85kW cooling capacity, making it ideal for commercial applications including offices, hotels, schools, and leisure facilities. This dual functionality eliminates the need for separate heating and cooling systems, reducing capital costs, installation complexity, and ongoing maintenance requirements. The systems can provide space heating via radiators or underfloor heating, domestic hot water production, and air conditioning during summer months. With flow temperatures up to 78°C at -22°C outdoor temperatures (Hybrox), these heat pumps work effectively with existing radiator systems in retrofit applications, whilst also being optimised for low-temperature systems in new builds. The ability to cascade multiple units allows heating capacities up to 1,600kW, making air source heat pumps suitable for large-scale commercial developments.

Future-proof technology
for decarbonisation

Air source heat pumps are at the forefront of the UK's transition away from fossil fuels, fully aligned with the Future Homes Standard and net-zero carbon commitments. Unlike gas boilers that burn fossil fuels, air source heat pumps extract renewable heat from the outdoor air and use electricity to transfer that heat into buildings. When powered by renewable electricity from solar panels or green tariffs, they offer a truly zero-carbon heating solution. The Modutherm range uses natural R290 refrigerant with a Global Warming Potential (GWP) of just 3, compared to thousands for synthetic refrigerants or the carbon emissions from gas combustion. This makes them one of the most environmentally responsible heating technologies available. With no combustion & no flue requirements, air source heat pumps eliminate carbon monoxide risks and reduce maintenance demands. As grid electricity continues to decarbonise, the environmental performance of heat pumps improves automatically, providing long-term sustainability without equipment replacement.

Scalable solutions for any project size

Air source heat pumps offer flexible, scalable solutions suitable for single dwellings through to large commercial developments. The Hybrox range (10-18kW) is ideal for individual apartments, houses, and small commercial properties, whilst the AW290 series (35-100kW, expanding to 100kW in Q3 2026) serves larger applications. Multiple units can be cascaded together to achieve heating capacities up to 1,600kW, making them suitable for hotels, apartment blocks, schools, leisure centres, and industrial facilities. This scalability provides design flexibility and allows systems to be sized precisely to match building loads, avoiding the inefficiencies of oversized equipment. Air source heat pumps can be installed as standalone systems or integrated into heat networks, combined with buffer vessels for hydraulic separation, or paired with thermal stores for domestic hot water production. The compact outdoor units equire minimal space making them suitable for properties with limited plant room space or restricted external areas.

Smart controls and system integration

Modutherm's air source heat pumps feature advanced controls and connectivity options that maximise efficiency, comfort, and ease of management. Smart controls optimise operation based on outdoor temperatures, occupancy patterns, and electricity tariffs, reducing running costs whilst maintaining precise indoor comfort levels. The systems integrate seamlessly with building management systems (BMS) via Modbus connectivity, enabling remote monitoring, performance analytics, and fault diagnostics. This connectivity is particularly valuable for commercial properties, housing associations, and multi-dwelling buildings where centralised management reduces operational overhead. Weather compensation adjusts output automatically based on outdoor conditions, eliminating temperature overshoots and improving comfort whilst reducing energy waste. The Modutherm range is compatible with smart home systems, time-of-use electricity tariffs, and demand-side response programmes, allowing operation to be scheduled when grid electricity is cheapest or greenest. When paired with solar PV systems, air source heat pumps can be configured to operate primarily when renewable electricity is being generated, further reducing energy costs and carbon emissions.

Technical Data
1116
Performance
Heating capacity / COP
(DIN EN 14511-x)
A10/W35 - Partial loadkW / COP3.69 / 5.63 5.61 / 5.90
A7/W35 - Partial loadkW / COP3.45 / 5.045.48 / 5.68
A7/W55 - Partial loadkW / COP3.20 / 3.03 4.94 / 3.29
A2/W35 - Partial loadkW / COP6.94 / 4.38 10.10 / 4.20
A-7/W35 - Partial loadkW / COP9.41 / 3.04 13.00 / 2.76
A-7/W55 - Partial loadkW / COP8.44 / 2.1512.69 / 2.15
Heating capacity
(min/max)
A10/W35kW3.69 / 10.00 5.61 / 13.00
A7/W35kW3.45 / 10.00 5.47 / 13.00
A7/W55kW3.20 / 10.00 4.94 / 13.00
A2/W35kW3.58 / 10.00 4.59 / 13.00
A-7/W35kW3.57 / 9.41 4.74 / 13.00
A-7/W55kW3.31 / 8.444.26 / 12.69
Cooling capacity / EERA35/W18 - Partial loadkW8.62 / 4.45 8.20 / 4.52
A35/W7 - Partial loadkW5.94 / 3.16 6.95 / 3.10
Cooling capacity
(min/max)
A35/W18kW3.67 / 10.005.59 / 12.00
A35/W7kW2.43 / 8.003.74 / 12.00
DHW heating capacitykW1013
Maximum flow temperature35°C & 55°CA+++
Maximum flow temperature°C78
Air flow rate at max external pressure m³/h4000
Flow rate (pipe dimensioning) l/h18002300
Minimum volume buffer tank in series / separation buffer tank litres88
Pressure loss at flow rate at 1800 l/hbar0.160.14
Maximum allowable operating pressure bar3
Operating limits
Heating circuit return/flow
(min/max)
Within operating temperatures °C20 / 65
Operating temperature
(min/max)
Heating°C-22 / 35
Average bivalence temperature
(DIN EN 14825)
Low / Medium°C-7 / 7
Sound
Sound power level
(min/night/max)
dB(A)45 / 52 / 6046 / 55 / 60
Sound power level
(DIN EN 12102-1)
dB(A)4946
General
Total weightkg170189
Refrigerating circuit maximum allowable operating pressure
(high pressure/low pressure)
MPa (g)3.15 / 2.1
Refrigerant type / capacity / kgR290 / 1.6R290 / 1.9
Safety valve — heating circuit response pressure bar3
Electrical
Voltage Heat pump supply3~N/PE/400V/50Hz
All-pole fuse protection ¹ ²Compressor onlyAB16
Control voltage fuse protection ²AB10
Effective power consumption
(DIN EN 14511-x)
A7/W35 — Partial loadkW0.680.97
Electrical consumptionA7/W35 — Partial loadA1.211.67
Power factorA7/W35 — Partial loadcosφ 0.990.97
Effective power consumption ¹
(min/max)
A7/W35kW0.58 / 2.170.95 / 2.78
Maximum machine current ¹A811.5
Maximum power consumption ¹Within operating limitskW68
IP protectionIP24
Residual current circuit breaker If requiredType B
Luxtronik wall controller
DimensionsH x W x Dmm535 x 330 x 166
Weightkg5.3
1 Compressor only | 2 Note legal regulations
21
Performance
Heating capacity / COP
(DIN EN 14511-x)
A10/W35 - Partial loadkW / COP7.23 / 5.68
A7/W35 - Partial loadkW / COP7.15 / 5.31
A7/W55 - Partial loadkW / COP6.90 / 2.05
A2/W35 - Partial loadkW / COP5.77 / 4.32
A-7/W35 - Partial loadkW / COP18.00 / 2.95
A-7/W55 - Partial loadkW / COP16.97 / 2.17
Heating capacity
(min/max)
A10/W35kW7.23 / 18.00
A7/W35kW7.15 / 18.00
A7/W55kW6.90 / 18.00
A2/W35kW5.77 / 18.00
A-7/W35kW6.12 / 18.00
A-7/W55kW5.66 / 16.97
Cooling capacity / EERA35/W18 - Partial loadkW7.23 / 4.71
A35/W7 - Partial loadkW5.33 / 3.46
Cooling capacity
(min/max)
A35/W18kW7.23 / 16.00
A35/W7kW5.33 / 16.00
DHW heating capacitykW18
Maximum flow temperature35°C / 55°CA+++ / A++
Maximum flow temperature°C78
Air flow rate at max external pressure m³/h9000
Flow rate (pipe dimensioning) l/h3300
Minimum volume buffer tank in series / separation buffer tank litres180
Pressure loss at flow rate at 3300 l/hbar0.28
Maximum allowable operating pressure bar3
Operating limits
Heating circuit return/flow
(min/max)
Within operating temperatures °C20 / 65
Operating temperature
(min/max)
Heating°C-22 / 35
Average bivalence temperature
(DIN EN 14825)
Low / Medium°C-7 / 7
Sound
Sound power level
(min/night/max)
dB(A)51 / 58 / 65
Sound power level
(DIN EN 12102-1)
dB(A)53
General
Total weightkg264
Refrigerating circuit maximum allowable operating pressure
(high pressure/low pressure)
MPa (g)3.15 / 3.00
Refrigerant type / capacity / kgR290 / 2.3
Safety valve — heating circuit response pressure bar3
Electrical
Voltage Heat pump supply3~N/PE/400V/50Hz
All-pole fuse protection ¹ ²Compressor onlyAB20
Control voltage fuse protection ²AB10
Effective power consumption
(DIN EN 14511-x)
A7/W35 — Partial loadkW1.35
Electrical consumptionA7/W35 — Partial loadA1.95
Power factorA7/W35 — Partial loadcosφ 0.96
Effective power consumption ¹
(min/max)
A7/W35kW1.35 / 3.82
Maximum machine current ¹A15
Maximum power consumption ¹Within operating limitskW11
IP protectionIP24
Residual current circuit breaker If requiredType B
Luxtronik wall controller
DimensionsH x W x Dmm535 x 330 x 166
Weightkg5.3
1 Compressor only | 2 Note legal regulations