Genesis WM

Condensing boilers

The Genesis wall-mounted condensing boiler is available in a range of 5 models from 41kW - 149kW, with a highly durable stainless steel heat exchanger offering an efficiency of up to 108% net. Cascade kits are available up to 6 boilers and 900kW output.

5

5 Year Heat Exchanger
Warranty*

2

2 Year Parts
Warranty*

ErP

ErP Part L
Compliant

  • Stainless steel heat exchanger

  • Natural gas or LPG

  • Cascade installations up to 900kW

  • Class 6 NOx emissions

  • First fix kit with integral isolation valves

  • High modulation ratios up to 10:1

  • 0-10V control

  • Integrated flue gas non-return valve

Downloads
Technical Data
Power
456085120150
Energy efficiency class (modules ≤ 70kW only)A-
Maximum boiler output (80-60°C) - NG & LPGkW38.558.377.8111.3135.7
Maximum boiler output (50-30°C) - NG & LPG kW41.562.884.8122.0148.7
Minimum boiler output (80-60°C) - NG & LPG kW3.85.88.511.121.6
Minimum boiler output (50-30°C) - NG & LPG kW4.36.59.712.423.9
Maximum boiler input (gross) - NG & LPGkW406081115140
Heat efficiency (50-30°C) - maximum output%105.3104.6104.8106.1106.2
Standby losseskW0.0850.0990.1140.0970.127
Modulation1:91:101:6
Building regulations Part L seasonal efficiency {Non Domestic Building}% gross95.695.995.896.395.8
SAP 2009 Annual efficiency {Natural Gas}%88.989.089.389.0
Sound power level indoorsdB(A)54596361
Hydraulic
Water contentlitres2.23.34.36.79.2
System design flow rate (30°C AT rise) single boilerl/s0.330.500.680.971.18
Water side pressure loss (30°C AT rise) single boilerkPa18.319.621.721.924.4
System design flow rate (20°C AT rise) cascadel/s0.500.751.011.461.78
Water side pressure loss (20°C AT rise) cascadekPa36.537.544.742.950.4
Minimum water pressurebar0.8
Maximum water pressurebar3.03.55.0
Maximum flow temperature setting°C80*
Gas
Maximum gas flow rate, NG (G20)m³/hr4.236.358.5712.1714.81
Maximum gas inlet pressure - NGmbar25
Nominal gas inlet pressure - NGmbar20
Minimum gas inlet pressure - NGmbar17
Maximum gas flow rate - LPG (G31) m³/hr1.642.453.314.705.73
Nominal gas inlet pressure - LPGmbar37
Flue
Approx. flue gas volume - NG @ 15°C, 9.1-9.3% CO2, @ N.T.P {dry}m³/hr46.069.895.3135.2164.7
Approx. flue gas volume - NG @ 15°C, 9.1-9.3% CO2, @ N.T.P {wet}m³/hr54.582.5112.4159.6194.3
Maximum flue gas temperature (80-60°C) - NG & LPG {Inlet Air at 20°C}°C77.065.374.072.6
Pressure at boiler flue spigot (80-60°C) - NG & LPG {Single boiler/individual flue applications}Pa190150194275290
Pressure at boiler flue spigot (80-60°C) - NG & LPG {Multiple boilers/combined flue applications}Pa30
Approx. flue gas volume - LPG (15°C, 10.3-10.5% CO) @ N.T.P {dry}m³/hr47.771.599.4138.4168.5
Approx. flue gas volume - LPG (15°C, 10.3-10.5% CO) @ N.T.P {wet}m³/hr54.281.3112.7157.2194.8
Dry NOx emmision (0% excess oxygen, mg/kWh dry air free)mg/kWh2339363040
Electric
Electrical supplyV230-250
Power consumption - maximum boiler modulation W94119156251310
Start current (per module) Amp4.0
Run current (per module) Amp4.0
Other
Dry weightkg45.550.074.584.5106.0

* 85°C for single boiler applications available on request