Single Coil
500 litres
Twin Coil
500 litres
Single Coil
800-1500 litres
Twin Coil
800-1500 litres
Storage Vessel
500-1000 litres
Storage Vessel
1500-3000 litres

Juniper® PW

The Juniper PW (Polywarm®) hot water calorifier is available as either a single coil or twin coil, and as a DHW storage vessel. The calorifier capacities range from 500-1500 litres, whilst the DHW storage vessel ranges from 500-3000 litres.

Single Coil

Polywarm® single coil. Available in a range of 4 models from 500-1500 litres.

In Stock

Available in
5-7 working days.

Twin Coil

Polywarm® twin coil. Available in a range of 4 models from 500-1500 litres.

Made to Order

Available in 5-6 weeks.

Storage Vessel

Polywarm® storage vessel. Available in a range of 7 models from 500-3000 litres.

Made to Order

Available in 5-6 weeks.

  • Single/twin coil calorifiers range from 500-1500 litres

  • DHW storage vessels range from 500-3000 litres

  • 8 calorifier models / 7 storage vessel models

  • Electric immersion elements (optional)
    (1.5-3kW single phase)
    (4kW-12kW three phase)

  • Unvented kits

  • Cathode protection

  • Digital control

  • Energy class C

*Subject to Terms & Conditions

View Technical Data
Downloads
Technical Data
50080010001500
Nominal storage capacitylitres49878910381443
Energy classC
Coil tube Ømm3242
Coil surface area1.82.73.53.8
Coil maximum operating temperature°C110
Coil maximum operating pressurebar12
Tank (secondary) maximum working temperature°C90
Tank (secondary) maximum working pressurebar108
Weight (empty/full)kg108 / 597188 / 977223 / 1261318 / 1761
Heat up time 50°C ΔT (immersion only)hr3.66.61.82.8
Immersion heater option (power/phase)kW/ph3 / 112 / 3
Standby loss at 65°CkWh/24hr2.42.83.23.9
Primary flow ratel/s0.9720.4861.670.8331.670.8331.670.833
m³/hr3.51.75636363
Continuous DHW output @ 50°CΔT (10/60°C) with primary 80°C on lower coill/h696.5634.61009.8928.51291.11175.61360.21235.9
10 minute peak DHW draw off @ 50°C ΔT (10/60°C) with primary 80°C on lower coil and tank warmed @ 60°Clitres614.1603.8927.3913.81253.21233.91675.41654
Recovery time DHW @ 50°C ΔT (10/60°C) full tank without draw off with primary 80°C on lower coilminutes5058.4556456657892
Nominal heat transferred by lower coil with primary 80°C and DHW @ 50°C ΔT (10/60°C)kW40.536.95853.374.167.47870.8
Lower coil primary hydraulic resistancekPa18.65.411.83.519.65.415.84.7
50080010001500
Nominal storage capacitylitres49878910381443
Energy classC
Coil tube Ømm3242
Lower coil surface area1.82.73.53.8
Upper coil surface area1.01.61.81.9
Coil maximum operating temperature°C110
Coil maximum operating pressurebar12
Tank (secondary) maximum working temperature°C90
Tank (secondary) maximum working pressurebar108
Weight (empty/full)kg108 / 597188 / 977223 / 1261318 / 1761
Heat up time 50°C ΔT (immersion only)hr3.66.61.82.8
Immersion heater option (power/phase)kW/ph3 / 112 / 3
Standby loss at 65°CkWh/24hr2.42.83.23.9
Primary flow ratel/s0.9720.4861.670.8331.670.8331.670.833
m³/hr3.51.75636363
Continuous DHW output @ 50°CΔT (10/60°C) with primary 80°C on lower coillitres/hour696.5634.61009.8928.51291.11175.61360.21235.9
10 minute peak DHW draw off @ 50°C ΔT (10/60°C) with primary 80°C on lower coil and tank warmed @ 60°Clitres614.1603.8927.3913.81253.21233.91675.41654
Recovery time DHW @ 50°C ΔT (10/60°C) full tank without draw off with primary 80°C on lower coilminutes5058.4556456657892
Nominal heat transferred by lower coil with primary 80°C and DHW @ 50°C ΔT (10/60°C)kW40.536.95853.374.167.47870.8
Continuous DHW output @ 50°C ΔT  (10/60°C) with primary 80°C on upper coillitres/hour399.0369.7572.5535.8683.7636.8720.3670.0
10 min peak DHW draw off @ 50°C ΔT  (10/60°C) with primary 80°C on upper coil and tank warmed @ 60°Clitres236.5231.6387.6381.0446.9439.1632.1623.7
Recovery time DHW @ 50°C ΔT  (10/60°C) full tank without draw off with primary 80°C on upper coilminutes29.232.732.036.037.141.741.046.0
Nominal heat transferred by upper coil with primary 80°C and DHW @ 50°C ΔT  (10/60°C)kW23.221.533.030.839.336.641.438.5
Continuous DHW output @ 50°C ΔT  (10/60°C) with primary 80°C on the lower & upper coillitres/hour1095.41004.31530.91393.81897.91697.62028.11808.0
10 minute peak DHW draw off @ 50°C ΔT  (10/60°C) with primary 80°C on on the lower & upper coil and tank warmed @ 60°Clitres680.6665.41014.2989.61354.31320.91781.01744.3
Recovery time DHW @ 50°C ΔT  (10/60°C) full tank without draw off with primary 80°C on the lower & upper coilminutes34.341.935.742.640.249.252.865.1
Nominal heat transferred by the lower & upper coil with primary 80°C and DHW @ 50°C ΔT  (10/60°C)kW63.758.487.879.3108.897.3116.2103.6
Lower coil primary hydraulic resistancekPa18.65.411.83.519.65.415.84.7
Upper coil primary hydraulic resistancekPa10.12.86.92.08.12.48.52.5
Lower & upper coil primary hydraulic resistancekPa28.78.218.75.527.77.824.47.2